Figure 7: MTG operating parameters as a function of time during test Microturbine output reacts without sensible delay to the changes in the bank load. The ramp-up rate is observed to be about 8 seconds for 0 to 20 kW. The ramp down rate is about 6 seconds for 20 to 3 kW. As for the fuel energy consumed, it is seen the fluctuation, associated to the mass flow rate adjustments, according to the control dynamics of the fuel valve and to the changes in fuel LHV and density. The variable speed control of the MTG relies on a system that sense load and optimize speed. Considering the heat value given by the chromatographic analysis of the LPG, the energy flows are converted to fuel flows, which allows to approximate also the air/fuel ratio. The variation of these magnitudes is shown in the figure 8. Performance of a Capstone Gas Turbine based Power Plant Working on High Butane LPG © 2022 Global Journals Global Journal of Researches in Engineering (A ) Volume XxXII Issue I Version I 24 Year 2022